Kinetrol® AS Interface Bus Commication
AS interface devices are used to make up control systems based on a two-wire communication cable known as a bus. These can be controlled or monitored by means of a digital signal sent via the bus to and from a “master” device (which can be a computer or a PLC).
Specifications
- Master – Slave protocol
- Up to 62 Slaves per Master (using extended addressing)
- Each Slave has its own unique address (set by user)
- All Slaves can be scanned every 5 milliseconds
- Baud Rate – 197 Kbits/second
- Slaves may be added anywhere in the bus
- Slaves may be parallel connected on the bus, using star or spur configurations
- Up to 124 inputs per bus
- Up to 124 outputs per bus, 62 using the Kinetrol device
- 26.5 to 31.5 Vdc, 8 A max power supply
- 100 m (325ft) maximum cable length (repeaters may extend network distance)
- Untwisted, unshielded, 2-wire (1.5mm2) cable can be used
Delivery Details
Net Weight: See catalogue page
Package Dimensions: See catalogue page
Commodity Code: See catalogue page
Country of Origin: United Kingdom
Documents
Kinetrol AS Interface Bus Communication Datasheet
Kinetrol AS Interface Bus Communication Catalogue Page